|
|
The power for your systems
|
Application Note: Linear Regulated DC Power Supplies
Datasheet PDF
AC Input Wiring and Fusing
The universal transformer allows four input voltage ranges -
100/117/220/230-240 VAC ±10%.
Before operation at a specific line voltage,
the proper input jumpers must be installed.
Adequate input fusing is also recommended.
For jumpering scheme and fusing requirements,
refer to the unit ID label or the table below:
| lnput (VAC) |
100 90-110 |
117 105-125 |
220 200-240 |
230/240 210-250
|
| Jumper |
1 - 2 3 - 4 |
1 - 2 3 - 4 |
2 - 3 |
2 - 3 |
| Apply AC |
1 - 5 |
1 - 4 |
1 - 5 |
1 - 4 |
| Schematic |
 |
 |
 |
 |
| Fuse |
See unit ID label.
Recommended 150% of output current. |
Jumpering Example: For operation at 117VAC,
Jumper 1-2 and 3-4; and apply AC input to 1 - 4.
|
DC Output Wiring
Local Sense
When load leads are not too long and remote regulation is not
required, simply connect the load to the output terminals marked
+Vo or +Out and -Vo or -Out. Load leads must never be connected
to the sense terminals. Open sense lead protection is built-in
and straping the sense leads to the output leads is not needed.
Remote Sense
All models above 30 watts are provided with remote sense
feature to compensate the load line drop and to permit a remote
point of regulation. The figure below shows proper wiring for a
power supply with remote sensing.
The remote sense can compensate a line drop of up to 0.25V. The
load leads must be sized so that the line drop does not exceed
0.25V - the lesser the better. To provide noise immunity, it is
recommended to use twisted pair or shielded pair for sense leads.
A small AC decoupling capacitor ( 0.1 to 10 µF) across
the sense terminal will also enhance the noise immunity. In
some applications, the power supply output tends to oscillate due
to the phase shift caused by the line resistance and inductance.
The addition of capacitor C1 will reduce output impedance and
provide stability. The recommended value of C1 is 100 µF
per ampere or 50 µF per foot of lead wire.
Grounding
The grounding, if not done right, can have a significant effect on
the over all system performance. A single point grounding
system should be employed, whenever possible, to eliminate
ground loops and to improve regulation.

Recommended |
|

Undesired |
Thermal Considerations
In normal operation the chassis gets hot due to the heat generated
in the regulator. An unrestricted mounting area is recommended.
Moving air is desirable in confined areas. The chassis may be
mounted on other heat dissipating surfaces to improve cooling.
Overvoltage Protection (OVP) Adjustment
The overvoltage is fixed on +5V outputs and is factory set at 6.2
±0.4V. On all other outputs, a separate universal OVP module
should be used. Single output units normally have their OVP
adjusted at 1 to 2 volts or 10 to 20% (whichever is greater) above
the nominal output voltage. For dual output units, the same
criteria applies above the sum of the two voltages. Adjust OVP
as follows:
- Adjust OVP adj. potentiometer fully clockwise.
- Apply AC input voltage.
- Adjust output voltage to the desired overvoltage trip point.
- Turn the OVP adj. potentiometer counterclockwise until
output voltage is crowbarred to approximately 1 volt.
- Switch the AC input off and adjust the output voltage down.
- Reapply AC input voltage and adjust the output up
to verify the set point.
Overload Adjustment
The overload is factory set at 110 to 120% and should not require
any adjustment. If this has been changed or require recalibration,
it can be accomplished as follows:
- Adjust OL adj. potentiometer fwly clockwise.
- Apply AC input voltage.
- Adjust output to the lowest voltage of the specified voltage range.
- Adjust the load current to 110 to 120% of rated output current.
- Slowly tum the OL adj. potentiometer counterclockwise
until the voltage starts decreasing.
©2001 PowerVolt, Inc.